Documented field work
Installation details and completed work


The need
The reported problem was a circuit without power. Although all breakers appeared to be in the “On” position, one breaker was not providing voltage and its handle mechanism was stuck in that position. The investigation also found signs of liquid contamination in the breaker panel and on cables above it.
PTX's approach
PTX investigated the circuit and inspected the panel, breakers, busbar and neutral bar. The inspection also considered the fresh-air duct above the panel. There was no liquid residue on the vent or floor, while some residue was found inside the duct and the liquid in the panel had dried. The recorded evidence suggested the contamination was not recent, but the specific cause and timing were not confirmed.
The recorded result
The circuit investigation identified a tripped breaker with a stuck handle and documented liquid penetration affecting some breakers, the busbar and the neutral bar. Based on those findings, replacement of the panel and all breakers was strongly recommended. A quote was to follow; no panel or breaker replacement was completed as part of this recorded service call.
What this job helps another property owner consider
When a circuit is without power even though a breaker appears to be switched on, the breaker mechanism and the wider panel condition may both need inspection. This job also shows why signs of liquid contamination should be documented before deciding whether replacement planning is needed.
Frequently asked questions
Questions property decision-makers ask
What was found during this Coquitlam electrical service call?
The investigation found one breaker without voltage. It had tripped, but its handle remained stuck in the “On” position. The inspection also documented dried liquid contamination in the panel, affecting some breakers, the busbar and the neutral bar.