Documented field work

Installation details and completed work

Wall-mounted light switch on a painted interior wall.
beforeElectrical service work involving a wall-mounted light switch.
Wall-mounted electrical switch and cover plate beside an interior doorway.
afterElectrical service work in an interior living space, showing a wall-mounted switch beside a doorway.
White wall-mounted electrical switch with a small illuminated indicator.
afterWall-mounted switch shown in an electrical service-work context.
Ceiling electrical work area showing a cable routed between an opening and a recessed light beside a window.
afterElectrical work in progress, with wiring routed between the ceiling opening and recessed light.

The need

The light was receiving only 23 volts. After the switch was removed, testing showed 120 volts at the switch. PTX traced the circuit to understand where the supply was being interrupted. The black wire traced back to the switch, but the white wire could not be traced beyond a screw in the cupboard, indicating the wire was broken at that point.

PTX's approach

PTX explained that a new wire would need to run from the switch to the light. Two holes were cut in the bulkhead to fish the new wire through. PTX then reinstalled the light fixture and switch. For a separate bedroom request, the existing switch was disconnected and removed, a Caséta switch was installed, and a wireless Pico switch was fitted and paired with it.

The recorded result

The new wire was fished from the light to the switch, and the light fixture and switch were reinstalled. The recorded work also includes installation and pairing of the Caséta switch and wireless Pico remote. The work was completed during the November 10, 2026 electrical service call.

What this job helps another property owner consider

When a light has an unusual voltage reading, the issue may require tracing the wiring rather than replacing the fixture. This job shows the value of checking voltage at more than one point and tracing the circuit before deciding whether a new wire is needed. Each property still needs its own assessment.

Frequently asked questions

Questions property decision-makers ask

Why might an electrician check voltage at both the light and the switch?

In this job, the light measured 23 volts while the switch measured 120 volts. Comparing those points helped PTX trace where the circuit was interrupted and determine that a new wire was needed between the light and switch.